Fire door inspection frequency: how often should they be checked?

A plain-English guide for managing agents, landlords and building owners in Dorset: what the law requires, what your Fire Risk Assessment should cover, and how to stay on top of it.

The short answer

That depends on the type of building. In England, the only fixed minimum intervals in law apply to blocks of flats taller than 11 metres. Everywhere else, fire doors have to stay in good repair and work as intended, and the Fire Risk Assessment should set how often they are checked.

Fire door check intervals by building type
BuildingHow oftenWhere it comes from
Flats over 11m: communal fire doors Once a quarter, as a minimum Fire Safety (England) Regulations 2022
Flats over 11m: flat entrance doors Once a year, as a minimum, on a best-endeavours basis Fire Safety (England) Regulations 2022
Other flats, HMOs, offices, schools, care homes and shops As set by the Fire Risk Assessment Regulatory Reform (Fire Safety) Order 2005

Blocks of flats over 11 metres

The Fire Safety (England) Regulations 2022 came into force in January 2023. For multi-occupied residential buildings over 11 metres tall, the responsible person must:

  • inspect communal fire doors at least once a quarter;
  • use best endeavours to inspect each flat entrance door once a year or more often;
  • keep a record of the checks, including any attempts to get access that did not succeed.

“Best endeavours” matters for flat entrance doors, because they sit inside a resident’s home. If a resident will not give access, the responsible person should keep a record of the attempts made and try again.

In every block of flats with two or more homes, whatever its height, residents must also be told that fire doors should be kept shut when not in use, that they must not tamper with self-closers, and that damaged or faulty doors should be reported.

All other buildings

The Regulatory Reform (Fire Safety) Order 2005 applies to almost every non-domestic building and to the common parts of blocks of flats and HMOs. Under it, fire safety measures, fire doors included, must be maintained in efficient working order and good repair.

The Order does not give a fixed interval. Instead, your Fire Risk Assessment should reflect how the building is used. As a guide:

  • six-monthly inspections are a common starting point;
  • doors in heavy use, such as school corridors, hospital and care home routes, or busy office stairs, often need checking more often;
  • new doors are worth checking more closely in their first year, as they settle on their hinges;
  • any door that has been damaged, altered or had new hardware fitted should be checked afterwards.

Who is responsible?

The “responsible person” is whoever has control of the premises: usually the employer, owner, landlord, freeholder or managing agent. In a block of flats this covers the communal fire doors and the flat entrance doors, because those doors protect the escape route that everyone shares.

In Dorset, the Fire Safety Order is enforced by Dorset & Wiltshire Fire and Rescue Service, which covers the whole county including Bournemouth, Christchurch and Poole. A clear record of regular inspections and the work done to put defects right is the best evidence that the doors are being managed properly.

Routine checks and professional inspections

A quick visual check by building staff, for example making sure doors close and latch, are not wedged open and have no obvious damage, is useful between inspections. It does not replace a full fire door inspection, which looks at gaps, seals, hinges, closers, glazing and hardware against the requirements of each doorset, and records the result door by door.

See what we check on every fire door, or contact us to arrange an inspection anywhere in Dorset.

Questions about inspection frequency

Is there a legal minimum for how often fire doors are inspected?

Only for some buildings. In England, the Fire Safety (England) Regulations 2022 set minimum checks for blocks of flats taller than 11 metres: communal fire doors once a quarter and each flat entrance door once a year, on a best-endeavours basis.

For other premises the law says fire safety measures, fire doors included, must be maintained in efficient working order and good repair, and the right interval comes from the Fire Risk Assessment.

How is a building’s height measured for the 11 metre rule?

The height is generally measured from ground level to the top of the floor surface of the highest storey, not to the roof. A building of around four or five storeys is often close to 11 metres, so check the figure for your own building.

Do landlords of HMOs need to have fire doors checked?

Under the Management of Houses in Multiple Occupation (England) Regulations 2006, HMO managers must keep the means of escape from fire in good order, and fire doors on escape routes are part of that. The Fire Safety Order applies to the common parts as well. Regular checks are the practical way to show that this is being done.

Who enforces fire safety law in Dorset?

Dorset & Wiltshire Fire and Rescue Service enforces the Regulatory Reform (Fire Safety) Order 2005 in Dorset, including Bournemouth, Christchurch and Poole. Local councils deal with housing standards such as HMO licensing.

What happens if an inspection finds defects?

The report lists each defect by door. We then give you a costed scope that shows which doors can be repaired and which need replacing, and we can carry out the work and provide records at handover.

This guide summarises the rules in England as at November 2026 and is not legal advice. Your Fire Risk Assessment, or the fire risk assessor who wrote it, should set the right interval for your building.